Overview
Operating Conditions
1. Altitude: ≤ 2000 meters;
2. The environment temperature: upper limit +40℃, lower limit -20℃;
3. The average relative humidity of the surrounding air is not more than 95% (25℃);
4. In a gas or steam environment without damaging insulation;
5. Fixed installation and use.
Model and meaning
Technical Data
Item | Unit | Parameter | |||
Rated voltage | V | 380/660/1140 | |||
Rated current | A | 100/400/500/550/630/690/800/880/1000/1100/1250/1600/2000/2500 | |||
Protection Rating | / | Not less than IP54 | |||
Rated Frequency | Hz | 50 |
Main Rated Parameters of Circuit Breaker
Item | Unit | Parameter |
Circuit Breaker Model | / | DW15-2500(In:2500A) |
Rated Voltage | V | 1140 |
Rated Operating Short-Circuit Breaking Capacity(lcs) | KA | 20(AC 1140V) |
Rated Ultimate Short-Circuit Breaking Capacity(lcu) | KA | 25(AC 1140V) |
Technical requirements
- General Requirements
- The switchgear shall comply with the provisions of this standard and be manufactured in accordance with the enclosure design and technical documentation approved by a nationally designated inspection body. In addition to fulfilling the technical requirements set forth herein, it shall also conform to the requirements of GB/T 12173-2008.
- Special Service Conditions
- Operating conditions that fall outside the prescribed ranges shall be considered special service conditions, and the equipment shall be manufactured in accordance with the agreement made with the user.
- Enclosure Fabrication and Tolerances
- The enclosure shall be manufactured in accordance with the specified drawings.
- The outer casing shall be welded from 2.5 mm high-quality cold-rolled steel plate, and the internal support structure shall be fabricated from 20mm – 330 mm high-quality cold-rolled steel plate.
- Power-On Operation
- Perform power-on operation to verify the correctness of the wiring.
- Cable Entry Device
- The cable entry device shall have no sharp edges to prevent damage to the cables.
- Any unused openings on the equipment enclosure for electrical connections or conduit entries shall be sealed with proper sealing components.
- Fasteners
- The fastener materials shall be compatible with the enclosure material, and the bolt diameter shall not be less than M6.
- Protection Rating
- The protection rating of the switchgear enclosure shall be no less than IP54.
- Enclosure Impact Test
- Shall comply with the requirements of GB/T 12173.
For more detailed information please see the pdf file above or contact us.