Operating Conditions
1. Ambient temperature: upper limit + 40℃, lower limit ‒25℃;
2. Altitude: ≤1000m;
3. Relative humidity: daily average 95%, monthly average 90%;
4. A place free from fire, explosion, and severe vibration;
5. The surrounding air is free from obvious pollution such as corrosive or flammable gases, water vapor, and conductive dust. and technical mea-sures.
Model and meaning
Technical Specification
Item | Unit | Parameters | |
Rated Voltage | kV | 12 | |
1min Power Frequency Withstand Voltage | To ground and between phases | 42 | |
fracture | 48 | ||
Lightning Impulse Voltage (peak) | To ground and between phases | 75 | |
fracture | 85 | ||
Rated Frequency | Hz | 50 | |
Load Switch | Rated Current | A | 630 |
Electrical Life at Rated Current | Times | more than 100 | |
Interrupting no-load Transformer Capacity | kVA | 1250 | |
Rated Heat Stable Appliance | kA/s | 20/4; Gounding Switch 20/2 | |
Rated Dynamic Stable Current (peak) | kA | 50 | |
Rated Short-circuit Closing Current (peak) | 50 | ||
Fuse rated current | 125 | ||
Combination Appliance | Rated Transfer Current | A | 870 |
Rated Short Circuit Breaking Current | 20 | ||
Equipped with Fuse Model | kA | S□LAJ-12 | |
Mechanical Life | Times | 2000; 10000 | |
Auxiliary Circuit 1min Power Frequency Withstand Voltage | kV | 2 | |
Working Voltage of Electric Operating Mechanism | V | AC DC 220; 110 | |
Protection Class | / | IP2X |
External Dimensions