The Five Prevention of High-Voltage Switchgear
2024-09-04

-
- After closing the vacuum circuit breaker carriage to the test position, the breaker carriage cannot move into the working position when attempting to close (to prevent closing with load).
- When the grounding knife inside the high-voltage switchgear is in the closed position, the breaker carriage cannot move into the working position to close (to prevent closing with grounding).
- While the vacuum circuit breaker inside the high-voltage switchgear is in operation, the front and rear doors of the cubicle are mechanically locked with the grounding knife (to prevent accidental entry into live compartments).
- During operation and closure of the vacuum circuit breaker inside the high-voltage switchgear, the grounding knife cannot be closed to engage (to prevent closure with live grounding).
- During operation and closure of the vacuum circuit breaker inside the high-voltage switchgear, the breaker carriage cannot be moved out of the working position (to prevent withdrawal with load).