YB-12 0.4 Prefabricated Substation

YB Series Prefabricated Substation, also known as Compact Substation or Pad-mounted Substation, integrates medium-voltage switchgear, distribution transformer, and low-voltage switchboard into a single, factory-assembled unit.
It features a compact structure, easy installation, short construction time, and high reliability, making it widely used in residential areas, commercial complexes, industrial zones, and renewable energy projects such as wind and solar farms.

Email to Us

Overview


YB series substation is a kind of compact power distribution device that integrates medium voltage electrical equipment, transformer, and low voltage electrical equipment. It can be used in high-rise buildings, building in urban and rural areas, residential communities, high-tech development areas, small and medium-size factories. mining areas, oil fields, temporary construction sites, and other premises. It also can be used for acceptance and distribution of power in the power distribution systems of 6-15KV, 50HZ (60HZ), ring main power distribution system, and double power supply or radiate terminal power distribution system.

Operating Conditions


1. Altitude:  1000m;

2. Ambient temperature: -25℃ ~+40℃;

3. Relative humidity: Daily average not exceeding 95%,Monthly average not exceeding 90%;

4. Installation location: A location free from fire, explosion hazards, conductive dust, chemical corrosive gases, and severe vibrations;

When the above normal use conditions are exceeded, the user can negotiate with the company.

 

Model and meaning


 

Technical Specification


Prefabricated Substation Parameter
Item Unit Parameter
MV Unit Rated frequency Hz 50
Rated Voltage V 7.2 12
Rated Current A 400、630
Transfer current A 1200-3150
Power Frequency Withstand Voltage (to ground/isolation break) KV 42/48
Lightning Impulse Withstand Voltage (ground/isolation fracture) KV 75/85
Rated Short-Circuit Breaking Current(injection fuse) KA 31.5
Rated Capacity kVA 30-2000
Tapping Range ±2×2.5%,±5%
Transformer Unit Connection Group Yyn0、Dyn11
Impedance Voltage % 4、4.5
LV Unit Rated Voltage V 220、380
Main Bus Rated Current A 50-4000
Branch Current A 5-800
Shell Protection Level(Standard) IP33D
Noise Level dB ≤50
Load Switch Parameter
Item Unit Parameters
FKN12-12 Load Switch FZN25-12 Vacuum Load Switch
Rated Voltage kV 12
Rated Frequency Hz 50
Rated Current A 630/125
Rated Breaking Load Current 630
Thermal Withstand Current kA/s 20/2 20/4
Dynamic Withstand Current kA 50
Rated Short-circuit Making Current(Peak) 50
Full Load Breaking Times Times 100
Mechanical Life 3000 5000
Rated Short-circuit Breaking Current
(phase to phase and to ground)/break
kV 42/48
Lightning Impulse Voltage (phase to phase and to ground)/break 75/85

 

Medium Voltage Fuse Parameters
Model Rated Voltage(kV) Breaking Current(A) Rated Current(kA) Fuse Rated Current(A)
UK Model Chinese Model
SDL※J XRNT-12 12 40 31.5 6.3/10/16/20/25/31.5/40
100 50/63/70/80/100
125 125

 

Low Voltage Circuit Breaker Parameters
Model Type of Release Rated Current of Release(A) Switching Capacity (kA/AC380V)
DW15-630 Thermal-magnetic 315/400/630 40
DW15-1000 630/800/1000 50
DW15-1600 1600
DW15-2500 1600/2000/2500 60
CW1-2000 Intelligent 630/800/1000/1250/1600/2000 65(80)
CW1-3200 2000/2500/3200

If you need more detailed information, please view the pdf document above or contact us.