YB6-12/0.4 Pad-mounted Substation(American-style)

The YB6 Series American-style Pad-mounted Substation is a compact and fully enclosed power distribution unit that seamlessly integrates a high-voltage load break switch, an oil-immersed transformer, and a low-voltage distribution system into a single cabinet. Specifically designed for outdoor installation, it offers strong environmental adaptability, safe front access operation, and excellent reliability. As a result, it is widely used in residential areas, commercial centers, and industrial power distribution systems.

Email to Us

Overview


The YB6 Series Pad-mounted Substation is developed by incorporating advanced foreign technology and adapting it to the actual needs of the domestic market. The product offers numerous advantages, including compact size, easy installation and maintenance, low noise, low energy loss, anti-theft design, strong overload capacity, and comprehensive protection.
It is ideally suited for use in new residential communities, green spaces, parks, stations, hotels, construction sites, airports, and other locations. The substation supports 10kV ring networks, dual power supplies, or terminal power supply systems, and integrates functions such as power transformation, metering, reactive power compensation, and system protection.

Operating Conditions


1. Altitude:  1000m;

2. Ambient temperature: -35℃ ~+40℃;

3. Relative humidity: Daily average not exceeding 95%,Monthly average not exceeding 90%;

4. Installation location: A location free from fire, explosion hazards, conductive dust, chemical corrosive gases, and severe vibrations;

 

Model and meaning


 

Technical Specification


Pad-mounted Substation Parameter
Item Unit Parameter
Rated Voltage kV 12/0.4(MV/LV)
Maxmium Operating Voltage 12(MV Side)
Rated Frequency Hz 50
Rated Capacity kVA 50-1600
1 min Power Frequency Withstand Voltage KV 35
Lightning Impulse Voltage 75
Cooling Method Oil immersion self-cooling
Breaking Current of High Voltage Backup Fuse kA 50
Plug-in Fuse Breaking Current 2.5
Ambient Temperature -35~40
Allowable Temperature Rise of the Coil 65
No-load Voltage Regulation +5% OR + 2×2.5%
Noise Level db 50
Protection Level IP43

If you need more detailed information, please view the pdf document above or contact us.