KYN28-24-1

KYN28-24 Withdrawable Metal-clad Switchgear

KYN28-24 (Z)(GZS1) Withdrawable Metal-clad Switchgear (here-inafter referred to as “switchgear”) is suitable for three-phase AC 50Hz power system, used to receive and distribute electric energy and control, protect and monitor circuits.

Get a Quote

Overview


KYN28-24 (Z)(GZS1) Withdrawable Metal-clad Switchgear (here-inafter referred to as “switchgear”) is suitable for three-phase AC 50Hz power system, used to receive and distribute electric energy and control, protect and monitor circuits.

This product complies with the following standards: GB3906-2006 “3.6-40.5kV AC metal-enclosed switchgear and controlgear”, GB/T11022 “Common technical re-quirements for high-voltage switchgear and controlgear standards”, IEC62271:200 “Rated voltage 1kV above 52 below AC metal-enclosed switchgear and control-gear”, DL/T404 “Technical conditions for ordering indoor AC high-voltage switch-gear”.

Operating Conditions


1. Ambient temperature: -15℃ ~+40℃;

2. Altitude: 1000m;

3. Relative humidity: daily average 95%, monthly average 90%;

4. Seismic resistance: 8 magnitude;

5. Occasions without flammable and explosive matter, without corrosive chemical and frequent severe vibration, without strong shake;

6. When used under normal environmental conditions exceeding those specified in GB3906, the user and the manufacturer shall negotiate.

 

Model and meaning


KYN28-24-model

 

Technical Specification


Item Unit Data
Rated voltage KV 24
Rated frequency Hz 50
Rated current(circuit breaker) A 630/ 1250/ 1600/ 2000/ 2500/ 3150/4000
Rated current(switchgear) A 630/1250/ 1600/ 2000/ 2500/ 3150/4000
Rated short-time withstand current (4s) KA 16/ 20/ 25/ 31.5/ 40/ 50
Rated peak withstand current※ KA 40/ 50/ 63/ 80/ 100/ 125
Rated short-circuit breaking current KA 16/ 20/ 25/ 31.5/ 40/ 50
Rated short-circuit making current※ KA 40/ 50/ 63/ 80/ 100/ 125
Rated insulation level 1min.P.F. withstand voltage Between Phases KV 65
Phases to Ground 79
Lightning impulse withstand voltage (peak) Between Phases KV 125
Phases to Ground 145
Protection class Enclosure: IP4X, IP2X (VCB Door opened)

Basic Structure Diagram of Switchgear


KYN28-24-diagram

If you need more information, please see the pdf document above or contact us.
Agent
1
Request Quotation

    Get in touch
    To assign a dedicated Power Quality Engineer for your project drawing and fast quotation, please verify your WhatsApp Number/Email:

    ×