KBS-12 Series Pad-mounted Switchgear Station(Outdoor RMU)

KBS-12 Series Pad-mounted Switchgear Station (Outdoor Ring Main Unit) adopts and incorporates advanced foreign technology. It integrates a 12kV switchgear, circuit breaker, load break switch, current and voltage transformers, 12kV PT, FTU/RTU for switch station automation, CCU for communication and control, 12kV metering and automatic reading devices, UPS power supply, and indicating instruments.

Get a Quote

Overview


KBS-12 Series Pad-mounted Switchgear Station (Outdoor Ring Main Unit) adopts and incorporates advanced foreign technology. It integrates a 12kV switchgear, circuit breaker, load break switch, current and voltage transformers, 12kV PT, FTU/RTU for switch station automation, CCU for communication and control, 12kV metering and automatic reading devices, UPS power supply, and indicating instruments.

All components are pre-installed, tested, and commissioned inside a movable, sealed, moisture-proof stainless steel enclosure. This design realizes the integration of primary and secondary systems in urban distribution networks, modularizes installation, shortens construction time, and significantly improves the reliability of urban power grid operations.

 

Model and meaning


kbs-12-model

 

Technical Specification


Item Unit Technical Requirement
Load Switchgear Combined Electrical Cabinet
Rated Voltage kV 12
Rated Frequency Hz 50
Rated Current A 630 200
Rated Load Breaking Current 630
Rated Short-time Withstand Current (RMS) kA 20
Rated Short-circuit Duration s 3
Rated Peak Withstand Current kA 50 / 63
Closed Loop Breaking Current A 630
Rated Cable Charging Breaking Current 25
Rated No-load Transformer Breaking Current 16
Rated Breaking Transfer Current 1750
Expected Short-circuit Breaking Current of Fuse (RMS) kA 63
Grounding Switch Short-term Withstand Current/Duration 25kA/s
Rated Current Breaking Times Times ≥200
Mechanical Life Times ≥2000
Annual Leakage Rate of SF6 Gas / No more than 1%

 

Overall and Installation Dimensions


kbs-12-diagram

NOTE:

  1. Brick walls shall be constructed using M5 cement mortar, with the inside surfaces and the external surfaces above ground finished with 1:2.5 cement mortar plastering.
  2. If the ground floor is located below the groundwater level, waterproofing treatment shall be applied; otherwise, seepage prevention treatment shall be carried out.
  3. Lintels shall be fabricated using Φ6 reinforcement bars and C20 concrete.
  4. The No.8 channel steel base shall be welded and assembled, then subjected to anti-corrosion treatment (the anti-corrosion method to be specified by the user).
  5. The No.8 channel steel base shall be placed in the foundation recess, fixed with bracing bars and concrete.
  6. The user may opt not to construct the cable pit (the section shown within the dashed line) depending on the specific site conditions.

 

Agent